Code Compliance
15% of this examThree rulebooks share this domain: the Florida Building Code's Mechanical and Energy Conservation volumes for installation and efficiency requirements, the refrigerant-management rules (EPA Section 608, taught in the Refrigerant Management unit of Refrigeration & Air Conditioning Technology — the EPA text itself is not an exam book), and the safety practices in the outline's Safety and Equipment area: cylinders, oxy-acetylene, brazing on a charged line, rigging and sling angles, lockout and capacitor discharge, confined spaces, compressed air and tools. The 608 questions are predictable — certification types, the venting prohibition, and the recover/recycle/reclaim ladder. The mechanical-code questions are lookups: attic access, condensate, combustion air, venting categories, clearances.
What the exam asks
- Section 608: the four certification types, the venting prohibition, and the recover, recycle, reclaim ladder.
- Mechanical code lookups: attic access, condensate drains, combustion air, vent categories and garage rules.
- Energy code checkpoints: load calculations, duct sealing and testing, and the Southeast SEER2 minimums.
- Shop and job-site safety numbers: acetylene pressure, cylinder fill, sling angles, lockout and ladders.
Part 1 of 4
Refrigerant rules: Section 608
These questions are the most predictable in the domain. Know the certification table, know that venting is off the table, and know what each step of the recover, recycle, reclaim ladder means.
Four certification types, one mapping
Type I covers small appliances, Type II high-pressure equipment (the residential AC world), Type III low-pressure equipment, and Universal covers all three. A technician who also works on small appliances needs Universal; one who services only high- and low-pressure equipment could hold Type II and Type III. This exact mapping is the most reliable 608 question on the exam.
Venting is prohibited — recover instead
Knowingly venting refrigerant during service, maintenance, repair, or disposal violates the Clean Air Act. Before opening a system, recover the charge into an approved recovery cylinder with certified recovery equipment. Only de minimis releases during good-faith recovery are excused.
Recover, recycle, reclaim are a ladder
Recover = remove and store, no processing required. Recycle = clean on site (oil separation, filtration) for reuse. Reclaim = reprocess to the purity standard for new refrigerant (AHRI 700), verified by chemical analysis — generally only a certified reclamation facility can do it.
Section 608 beyond the certification types
Refrigerant is sold only to certified technicians or their employers, and sellers keep records. Hoses need low-loss fittings. Recovery machines must be certified; a vacuum pump is not recovery equipment. A disposable cylinder is recovered to empty before it is scrapped and is never refilled. Leak rate is the percent of the full charge that would be lost over 12 months, and an appliance over its allowed rate must be repaired and verified.
Leak rate = Loss projected over 12 months at the observed rate ÷ Full charge × 100
Loss projected over 12 months
1 lb ÷ 3 months × 12 equals 4.0 lb
Leak rate
12-month loss ÷ 20 lb equals 20%
In your books: The EPA text itself is not an exam book. The refrigerant management unit of Refrigeration & Air Conditioning Technology covers 608. The venting and reclaim definitions sit on adjacent pages, so tab them together.
Part 2 of 4
Mechanical code: look it up, then install to it
Mechanical code questions are lookups. The answer is a printed number, so the skill is knowing where to find it and what the common numbers are.
Code questions get looked up, not remembered
Minimum efficiency ratings, ventilation rates, condensate disposal, and equipment installation rules change with code editions. When a stem says 'minimum', 'required', or 'permitted', go to the FBC volume on your desk and read the current number — never answer from memory.
Listed, permitted, and reachable
Equipment must be listed and labeled and installed to the listing and the manufacturer's instructions, which makes those instructions enforceable. A change-out needs a permit even when the new unit matches the old capacity. Every appliance has to stay reachable for service and replacement without removing permanent construction. Attic units need the passageway, 24-inch solid flooring, a light switched at the opening, and a receptacle.
Mechanical code installation numbers
Attic passageway 30 in. high × 22 in. wide, not over 20 ft, with a 30 × 30 platform, light and receptacle; 3/4-in. primary condensate drain plus auxiliary pan or shutoff switch; combustion air 50 cu ft per 1,000 Btu/h indoors or two openings at 1 sq in. per 4,000 Btu/h direct to outdoors; Category I appliances on Type B vent, Category IV on the listed plastic vent.
Indoor air = 50 cu ft per 1,000 Btu/h. Two outdoor openings, each = Input ÷ 4,000 (direct or vertical duct) or Input ÷ 2,000 (horizontal duct) sq in. One outdoor opening = Input ÷ 3,000 sq in.
Indoor method: room volume needed
100,000 Btu/h ÷ 1,000 × 50 equals 5,000 cu ft
Outdoor, direct or vertical ducts: each of two openings
100,000 Btu/h ÷ 4,000 equals 25 sq in.
Outdoor, horizontal ducts: each of two openings
100,000 Btu/h ÷ 2,000 equals 50 sq in.
Outdoor, one opening instead of two
100,000 Btu/h ÷ 3,000 equals 33.3 sq in.
Condensate: slope it, trap it, back it up
The primary drain is at least 3/4 inch, sloped at least 1/8 inch per foot to an approved place of disposal, and trapped on a draw-through coil so the blower cannot hold water in the pan. Where an overflow would cause damage, add an auxiliary pan with its own drain to a conspicuous spot, or a water-level switch that shuts the unit down. The secondary drain never ties into the primary, and it should drip where someone will notice.
Fall = Run in feet × 1/8 in. per foot
Minimum drop over the run
40 ft × 1/8 equals 5.0 in.
In your books: Start at the definitions chapter of the FBC volume when a term seems slippery, then jump to the ventilation tables.
Part 3 of 4
Where equipment goes: location, Florida conditions, energy and smoke
Code also decides where fuel-burning equipment may sit, how it is anchored in Florida weather, and what the energy code checks on the way out. Plenums and machinery rooms add the fire and leak side.
Where fuel-burning equipment may sit
In a garage, ignition sources are raised at least 18 inches above the floor because gasoline vapor pools low; vapor-ignition-resistant appliances are exempt. Ordinary fuel-burning appliances are barred from sleeping rooms and bathrooms unless they are direct-vent or sealed-combustion. A fuel-burning appliance in a confined space needs combustion air openings sized to its input.
Florida installation: wind, flood and sun
Condensing units are anchored to resist the site's design wind speed, for uplift and overturning. In a flood hazard area equipment sits at or above the required flood elevation. Suction line insulation exposed to weather is protected from UV. Outdoor service ports get locking tamper-resistant caps. Refrigerant piping near the face of a stud gets a steel shield plate.
Energy code checkpoints
Equipment is sized from a calculated load (Manual J or equivalent) and selected by an accepted method (Manual S). Ducts and air handlers are sealed, and systems with ducts or the air handler outside the thermal envelope are pressure tested; ducts entirely inside conditioned space are the main exception. Thermostats must be able to schedule setbacks. Minimum efficiency in the Southeast is higher than the national number.
Plenums, smoke and machinery rooms
Materials in a ceiling plenum must be noncombustible or plenum-listed (the 25/50 rating), with no combustible storage or fuel-fired equipment. Duct smoke detectors on larger systems shut the air handler down so the ducts do not spread smoke. A refrigerant machinery room pairs a refrigerant detector with mechanical exhaust that starts when a leak is sensed.
Worked example
- North region13.4 SEER2
The national minimum
- Southeast, 45,000 Btu/h and larger13.8 SEER2
- Southeast, under 45,000 Btu/h14.3 SEER2
Florida. The same bar as the old 15 SEER
In your books: For energy questions, go to the energy-efficiency tables in the FBC volume. The answer is a printed number, not a judgment call.
Part 4 of 4
Safety on the job
Safety is 9% of this domain and mostly common sense with numbers. Cylinders, flame, lifting, electricity and ladders each have a short list of rules.
Safety is 9% and mostly common sense with numbers
Acetylene under 15 psig, cylinders upright and secured, flashback arrestors; never heat a cylinder with a torch, never fill a recovery cylinder past 80%; recover and nitrogen-sweep before brazing (phosgene); no one under a suspended load; sling tension doubles at a 30° angle; your own lock and tag, prove dead with a meter, discharge capacitors through a resistor; refrigerant pools in pits and displaces oxygen.
Leg tension = (Load ÷ Legs) ÷ Sine of the angle from horizontal
Share of the load per leg with the legs vertical
2,000 lb ÷ 2 equals 1,000 lb
Tension in each leg at this angle
(2,000 lb ÷ 2) ÷ 0.50 equals 2,000 lb
Ladders and working space
An extension ladder extends at least 3 feet above the landing and sits at about 4 to 1: one foot out for every four feet up. Electrical equipment that may be serviced live, like the disconnect, needs about 36 inches of clear working depth, outdoors included. The disconnect is within sight of the unit and readily accessible. The nameplate is the authority on refrigerant type, charge, voltage and ampacity.
Foot of the ladder out = Height up the wall ÷ 4
Distance from the wall to the foot of the ladder
16 ft ÷ 4 equals 4 ft
In your books: Safety questions are answered from the Safety unit at the front of Refrigeration & Air Conditioning Technology. OSHA's own standards are not on the list. Tab that unit and the refrigerant-handling pages.
Know these cold
The short list to have in your head on exam day. Every line is also a card in your flashcards.
- EPA 608 Type I
- Small appliances (5 lb or less of refrigerant)
- EPA 608 Type II
- High-pressure equipment — residential and commercial AC, heat pumps
- EPA 608 Type III
- Low-pressure equipment (e.g., centrifugal chillers)
- Universal certification
- All three types: the credential for a technician who works across every category
- Venting prohibition
- No knowing release during service or disposal; recover with certified equipment
- Reclaim standard
- Reprocessed to new-refrigerant purity (AHRI 700) and chemically verified
- Acetylene working pressure
- Below 15 psig.
- Recovery cylinder fill
- No more than 80% by weight; DOT-approved, in date, never heated with a torch.
- Sling angle
- Leg tension = (load ÷ legs) ÷ sin(angle). At 30° from horizontal each leg carries the full load.
- Cleaning air pressure
- 30 psig or less at the nozzle, with chip guarding and eye protection.
- Condensate drain slope
- At least 1/8 in. per foot (about 1%) toward the discharge.
- Primary condensate drain size
- Not less than 3/4 in. nominal.
- Auxiliary drain pan
- At least 1-1/2 in. deep, extending at least 3 in. beyond the unit, with its own drain to a conspicuous location.
- Float switch
- An accepted substitute for the auxiliary drain line: it stops the equipment before the pan overflows.
- Attic equipment access
- Passageway 30 in. high × 22 in. wide, not over 20 ft long, 24-in. solid flooring, 30 × 30 in. service space, light and receptacle.
- Ignition sources in a garage
- At least 18 in. above the floor (flammable-vapor-ignition-resistant appliances are exempt).
- Combustion air, indoor method
- 50 cu ft of room volume per 1,000 Btu/h of input (5,000 cu ft for 100,000 Btu/h).
- Combustion air openings to outdoors
- Two openings, each 1 sq in. per 4,000 Btu/h direct or by vertical duct, 1 per 2,000 by horizontal duct; or one opening at 1 sq in. per 3,000 Btu/h.
- Vent categories
- Category I: negative pressure, non-condensing, Type B vent. Category IV: positive pressure, condensing, the listed plastic or special vent.
- Southeast minimum, split AC
- 14.3 SEER2 under 45,000 Btu/h; 13.8 SEER2 at 45,000 Btu/h and larger. North: 13.4 SEER2. Judged by installation date in the Southeast.
- HSPF2
- Heating-season efficiency of a heat pump: seasonal Btu of heat ÷ watt-hours used. The heating counterpart to SEER2.
- Duct leakage test exception
- Ducts and air handler located entirely inside the conditioned space.
- Refrigerant sales restriction
- Sold only to certified technicians or employers buying for them; the seller keeps records.
- Low-loss fittings
- Required on recovery, recycling and charging hoses; they close automatically or by hand.
- Leak rate
- Percent of the full charge that would be lost over 12 months at the observed rate.
- Disposable cylinders
- Recover the remaining vapor, then scrap. Never refill one.
- Extension ladder
- Rails 3 ft above the landing; set at 4 to 1.
- Electrical working clearance
- About 36 in. deep in front of a disconnect at 120/240 V.
- Capacitor discharge
- Through a resistor (roughly 20 kΩ, 2 W) with insulated leads, never by shorting the terminals.
Where it lives in your books
The real exam is open book. Knowing which book and which tab answer this topic is worth as much as memorizing it.
- Florida Building Code · 18 recommended tabsCode questions give themselves away with words like 'minimum', 'required', or 'permitted'. Go to the code — never answer a code question from memory when the book is on the desk.
- HVAC References · 16 recommended tabsRACT is a 1,700-page textbook — it answers almost any fundamentals, electrical, or troubleshooting question, but only if you tab it by unit. Build the tab set below and trust the symptom tables over memory.
- EPA 608 · 2 recommended tabsCertification types are the classic question: Type I small appliances, II high-pressure, III low-pressure, Universal all three.
Reading isn't learning. Retrieval is.
79 questions in this domain, each with an explanation and source.