Load Calculation & System Design
20% of this examThe heaviest domain on the trade exam, built around the design sequence the ACCA manuals describe: calculate the load, select the equipment, size the ducts. The ACCA manuals themselves are not on the exam reference list, so the room books for this material are Energy Efficient Building Construction in Florida (loads, R and U values, the energy code), the Florida Energy Conservation code (equipment sizing in R403.7, duct and envelope testing), the Trane Ductulator (duct sizing) and the psychrometrics and air-side formulas in Refrigeration & Air Conditioning Technology. Expect tonnage conversions, sensible-vs-latent questions, air-side math (1.08 and 4.5), thermal-resistance arithmetic, SEER2 conversations with owners, and scenarios that punish rule-of-thumb sizing — Florida's humidity makes the oversizing trap real.
What the exam asks
- Which ACCA manual does which job: J for load, S for equipment, D for ducts.
- Tonnage conversions and sensible versus latent capacity, with the oversizing trap in a humid climate.
- Air-side math: 1.08 for sensible, 4.5 for total heat, 0.68 for latent, rearranged to solve for airflow or temperature.
- Building load arithmetic: R and U values, watts to Btu/h, air changes to CFM and room-by-room airflow.
- Heat pump balance point and strip heat sized for the deficit only.
Part 1 of 4
The design sequence: J, then S, then D
Load design runs in a fixed order. The building sets the load, the load picks the equipment, and the equipment's airflow sizes the ducts. Skip a step or guess at one and Florida's humidity finds the mistake.
J, then S, then D — in that order
Manual J computes the heating and cooling load from the building itself: envelope, windows and orientation, infiltration, internal gains, occupants. Manual S picks equipment whose actual rated performance covers that load at design conditions. Manual D sizes the ducts to deliver the airflow. Questions love to test which manual does which job.
Tons = Btu/h ÷ 12,000. Btu/h = Tons × 12,000.
Load in tons
42,000 Btu/h ÷ 12,000 equals 3.5 tons
Equipment capacity
5 tons × 12,000 equals 60,000 Btu/h
The old unit's nameplate is not an input
Loads come from the building, never from the equipment being replaced — the original unit may have been sized wrong, and the house may have changed. 'Match the existing tonnage' is always the wrong answer.
Oversizing is the classic trap
An oversized unit satisfies the thermostat fast, short cycles, and never runs long enough to wring moisture out of the air. Cold-but-clammy complaints on a new install point to oversizing, not undersizing.
In your books: None of the ACCA manuals are allowed in the room. Load questions are answered from Energy Efficient Building Construction in Florida and R403.7 of the Energy Conservation code. Duct sizing goes to the Ductulator. Tonnage is arithmetic, not lookup: write 12,000 Btu/h per ton on your scratch paper at the start of the exam.
Part 2 of 4
What puts load on the building
Manual J starts from the building itself. Design conditions, the envelope, glass, people, lights and leaks each add Btu/h, and the room-by-room split is what the ducts get sized from.
Design conditions come from tables, not from records
Indoor cooling design is about 75°F dry bulb and 50% relative humidity. Outdoor design comes from published climate data for the location: the 1% temperature is exceeded only about 1% of the cooling hours. Sizing to the all-time record oversizes the system for the rest of the year. The heating load is figured for a cold night with no solar gain and no internal gains, which keeps it conservative.
R-values add, U is the reciprocal
Layers in series: add every R-value (including the inside and outside air films), then U = 1 ÷ R total. Heat gain = U × area × ΔT. The energy code states envelope requirements as maximum U-factors or minimum R-values, and the EEBC book has the tables.
R total = sum of layers. U = 1 ÷ R total. Heat gain = U × Area × ΔT.
R total
15 + 4 + 1 equals 20
U-factor
1 ÷ R total equals 0.05
Heat gain through the wall
U × 500 sq ft × 30 °F equals 750 Btu/h
Glass, orientation and shade
SHGC is the fraction of the sun's energy that gets through the glazing, so a lower number means less cooling load. West glass is the worst exposure because it takes low-angle sun in the hottest part of the afternoon. An overhang shades south glass at midday when the sun is high, but does little for west glass. Exterior shading stops the heat before it reaches the glass; interior blinds re-release most of what they absorb into the room.
Internal gains: watts and people
Every watt of lighting, electronics or appliance power ends up as heat in the space at 3.412 Btu/h per watt, so 1,000 W is 3,412 Btu/h of sensible gain. The Manual J default for occupants is the number of bedrooms plus one, and each person adds both sensible and latent heat. Padding the occupant count is a common way a load gets inflated into oversized equipment. Lighting adds no moisture, so it never touches the latent load.
Btu/h = Watts × 3.412
Sensible gain
1,000 W × 3.412 equals 3,412 Btu/h
Infiltration is accidental, ventilation is on purpose
Infiltration is uncontrolled leakage driven by wind and stack effect. Ventilation is outdoor air brought in deliberately at a known rate. Both carry sensible and latent load. To turn air changes into airflow, multiply the volume by the ACH and divide by 60: a 12,000 cu ft house at 0.5 ACH leaks 100 CFM. An exhaust-only fan puts the house under negative pressure and pulls humid outdoor air in through every crack.
CFM = Volume × ACH ÷ 60
Infiltration airflow
12,000 cu ft × 0.50 ACH ÷ 60 equals 100 CFM
Attic ducts and room-by-room loads
Ducts in a hot attic gain heat through their walls and lose air through leaks, so Manual J adds a duct load. A return leak in a vented attic is the worst case: it sucks in hot, wet, unfiltered air ahead of the coil. A block load sizes the equipment; a room-by-room load is what sizes the ducts, because supply air is split in proportion to each room's share. A bedroom with 20% of the load gets 20% of the airflow.
Room CFM = Room load ÷ Block load × Total CFM
Share of the load
4,500 Btu/h ÷ 22,500 Btu/h equals 20%
Airflow to the room
4,500 Btu/h ÷ 22,500 Btu/h × 1,000 CFM equals 200 CFM
In your books: Energy Efficient Building Construction in Florida has the tables for loads, R and U values and the energy code. Tab the envelope requirement tables.
Part 3 of 4
Air-side math and the psychrometric chart
Sensible and latent loads are different problems. This is the arithmetic that moves heat and moisture with air, and the formulas the exam rearranges in every direction.
Sensible vs latent, dry bulb vs dew point
Sensible load lowers air temperature; latent load condenses moisture out of the air without changing temperature. Any surface colder than the air's dew point will sweat — that's the physics behind condensation on grilles and uninsulated ducts.
SHR = Sensible ÷ Total. Latent = Total − Sensible.
Latent load
36,000 Btu/h − 27,000 Btu/h equals 9,000 Btu/h
Sensible heat ratio
27,000 Btu/h ÷ 36,000 Btu/h equals 0.75
Reading the psychrometric chart
Any two independent properties fix one point on the chart, and everything else is read from it. Wet bulb reads below dry bulb unless the air is saturated. Cooling air without removing moisture raises its relative humidity. A coil removes moisture only when its surface is below the air's dew point. When two airstreams mix, the result is the flow-weighted average, so it lands closer to the larger stream.
Mixed temp = (CFM1 × T1 + CFM2 × T2) ÷ (CFM1 + CFM2)
Mixed-air temperature
(600 CFM × 75 °F + 200 CFM × 95 °F) ÷ (600 CFM + 200 CFM) equals 80 °F
Two air-side formulas carry the testing area
Sensible heat = 1.08 × CFM × ΔT (dry-bulb change). Total heat = 4.5 × CFM × Δh (enthalpy change read from the psychrometric chart). Airflow itself = duct area in square feet × velocity in feet per minute. Three formulas answer most of the 'determine air volume / enthalpy change' items in the outline's testing area.
Btu/h = 1.08 × CFM × ΔT
Sensible heat
1.08 × 1,200 CFM × 20 °F equals 25,920 Btu/h
Btu/h = 4.5 × CFM × Δh
Total heat (sensible plus latent)
4.5 × 1,000 CFM × 8 Btu/lb equals 36,000 Btu/h
CFM = Duct area (sq ft) × Velocity (fpm)
Airflow
2 sq ft × 600 fpm equals 1,200 CFM
Latent math runs on grains
Latent heat = 0.68 × CFM × the grain difference. Humidity ratio is the actual weight of water vapor in each pound of dry air, counted in grains, with 7,000 grains to the pound. 100 CFM of infiltration carrying 30 extra grains is 0.68 × 100 × 30 = 2,040 Btu/h the coil has to remove. Dropping the 0.68 is the planted wrong answer, the same way dropping the 1.08 is on sensible problems.
Latent Btu/h = 0.68 × CFM × Δgrains
Grain difference
90 − 60 equals 30 grains
Latent load
0.68 × 1,000 CFM × grain difference equals 20,400 Btu/h
Solve the air formulas in every direction
The exam rearranges 1.08 × CFM × ΔT. Airflow for a load: CFM = Btu/h ÷ (1.08 × ΔT), so 27,000 ÷ (1.08 × 20) = 1,250 CFM. Supply temperature for a load: ΔT = 25,920 ÷ (1.08 × 1,200) = 20°F, so a 75°F room needs 55°F supply air. ΔT is always the difference between the two air temperatures, never the indoor or outdoor reading by itself.
CFM = Btu/h ÷ (1.08 × ΔT)
Airflow needed
27,000 Btu/h ÷ (1.08 × 20 °F) equals 1,250 CFM
ΔT = Btu/h ÷ (1.08 × CFM). Supply = Room − ΔT.
Temperature change
25,920 Btu/h ÷ (1.08 × 1,200 CFM) equals 20 °F
Supply air temperature
75 °F − ΔT equals 55 °F
In your books: The psychrometrics and air-side formulas are in Refrigeration & Air Conditioning Technology. Tab the chart.
Part 4 of 4
Heat pumps and the balance point
In Florida the heat pump is selected against the cooling load. The heating side is about what happens on the coldest nights, and how much strip heat makes up the gap.
Heat pumps: balance point and strip heat
As the outdoor temperature falls, a heat pump's capacity drops while the building's heat loss rises. The balance point is the outdoor temperature where the two lines cross; below it, supplemental heat makes up the difference. Size the strips for the deficit only, at 3,412 Btu/h per kW. In Florida the heat pump is selected against the cooling load, and a tighter envelope moves the balance point colder.
Strip kW = (Heat loss − Heat pump output) ÷ 3,412
Deficit
30,000 Btu/h − 18,000 Btu/h equals 12,000 Btu/h
Strip heat needed
deficit ÷ 3,412 equals 3.5 kW
Know these cold
The short list to have in your head on exam day. Every line is also a card in your flashcards.
- One ton of cooling
- 12,000 Btu/h — divide total Btu/h by 12,000 to get tons (42,000 Btu/h = 3.5 tons)
- Manual J
- Residential heating/cooling load calculation
- Manual S
- Equipment selection — verify sensible AND latent capacity from expanded performance data, not nominal tonnage
- Manual D
- Duct system design and sizing from the Manual J airflows
- Latent load
- Heat removed to condense water vapor — large in Florida; oversized units fail it
- Dew point
- Temperature where air saturates — surfaces below it condense moisture
- Sensible heat formula
- Btu/h = 1.08 × CFM × ΔT (°F), standard air.
- Total heat formula
- Btu/h = 4.5 × CFM × Δh (Btu/lb of dry air, from the psychrometric chart).
- SEER2 vs SEER
- SEER2 uses the newer DOE test with higher external static (0.5 in. w.c.); the same unit rates lower in SEER2. Not interchangeable with SEER.
- Duct leakage test
- Duct pressurization fan at 25 Pa with registers sealed; result in CFM per 100 sq ft of conditioned floor area. Blower door at 50 Pa (ACH50) is the envelope test.
- Form R405
- Florida's residential performance-method energy calculation; the HVAC equipment listed on it must match what is installed.
- Latent heat formula
- Btu/h = 0.68 × CFM × grain difference (grains of moisture per pound of dry air).
- Grains of moisture
- 7,000 grains = 1 pound of water. Humidity ratio is an actual weight, unlike relative humidity.
- Where 1.08 comes from
- 0.075 lb/cu ft (air density) × 0.24 Btu/lb·°F (specific heat) × 60 minutes per hour.
- Watts to Btu/h
- 3.412 Btu/h per watt, so 1 kW = 3,412 Btu/h.
- Indoor cooling design condition
- About 75°F dry bulb and 50% relative humidity.
- Outdoor design temperature
- The 1% value from published climate tables for the location, not the record high and not the average.
- Manual J occupant default
- Number of bedrooms plus one (a 3-bedroom home = 4 people).
- ACH to CFM
- Volume × air changes per hour ÷ 60 (12,000 cu ft × 0.5 ÷ 60 = 100 CFM).
- Conduction load
- Q = U × area × ΔT (0.05 × 500 sq ft × 30°F = 750 Btu/h). Doubling the R-value halves the flow.
- SHGC
- Fraction of solar energy that passes through the glass. Lower SHGC = less cooling load.
- Sensible heat ratio (SHR)
- Sensible ÷ total capacity. An SHR of 0.70 leaves 30% for moisture removal; the lower SHR suits a humid load.
- Latent from total
- Latent = total − sensible (36,000 − 27,000 = 9,000 Btu/h).
- Heat pump balance point
- Outdoor temperature where heat pump capacity equals the building's heat loss. Below it, supplemental heat runs.
- Typical coil temperature drop
- About 20°F: 75°F return air leaves at about 55°F.
- Slab-on-grade loss
- Figured per linear foot of exposed perimeter, because the loss concentrates at the slab edge.
- Bypass factor
- The share of air that passes through a coil untreated. More rows and tighter fins = lower bypass factor.
- Indoor humidity target
- Around 50 to 55% RH, kept below the roughly 60% range where mold and dust mites take off.
Where it lives in your books
The real exam is open book. Knowing which book and which tab answer this topic is worth as much as memorizing it.
- Energy Efficient Construction FL · 6 recommended tabsEnergy questions are definition and direction questions: which way R and U go, what a blower door measures, where the vapor retarder sits in a Florida wall. The tables of R-values and the blower-door section answer most of them.
- Florida Building Code · 18 recommended tabsCode questions give themselves away with words like 'minimum', 'required', or 'permitted'. Go to the code — never answer a code question from memory when the book is on the desk.
- Ductulator · 5 recommended tabsDuct sizing questions on the exam are Ductulator questions: given CFM and a friction rate (commonly 0.08 to 0.1 in. w.c. per 100 ft), read the round size, then the rectangular equivalent that fits the space. Practice the dial until you can read it in seconds — it is faster than any table.
- HVAC References · 16 recommended tabsRACT is a 1,700-page textbook — it answers almost any fundamentals, electrical, or troubleshooting question, but only if you tab it by unit. Build the tab set below and trust the symptom tables over memory.